Power Cable Pulling: FRICTION_COEFFICIENT

Power cable pulling tension limits, sidewall bearing pressure limits, friction coefficients, jam ratio thresholds, minimum bend radius multipliers, and NEC conduit fill limits. Covers copper (K=0.008) and aluminum (K=0.006) max tension by AWG/kcmil per ICEA P-79-561 / IEEE 1185-2019; SWBP limits for XLPE, EPR, PVC, armored, and lead-sheathed cables; COF by conduit type (steel/PVC/HDPE/FRP) and lubrication condition; jam ratio safe zones (danger: 2.7–3.1); NEC 300.34 bend radius multipliers.

Electrical Engineeringparameter_type: FRICTION_COEFFICIENT3 rows
parameter typerecord idconduit typeinsulation typelubricant typenotesvalue maxvalue minvalue typical
FRICTION_COEFFICIENTCOF_DRY_PVC_CONDUITPVC_conduitanydryPVC conduit without lubricant0.50.350.45
FRICTION_COEFFICIENTCOF_DRY_STEEL_CONDUITsteel_conduitanydryRigid galvanized steel (GRC/IMC) conduit, no lubricant; use 0.5 as conservative default0.60.40.5
FRICTION_COEFFICIENTCOF_FIBERGLASS_DUCTfiberglass_ductanypolymer_compoundFiberglass reinforced plastic (FRP) duct with lubricant0.20.10.15