Power cable pulling tension limits, sidewall bearing pressure limits, friction coefficients, jam ratio thresholds, minimum bend radius multipliers, and NEC conduit fill limits. Covers copper (K=0.008) and aluminum (K=0.006) max tension by AWG/kcmil per ICEA P-79-561 / IEEE 1185-2019; SWBP limits for XLPE, EPR, PVC, armored, and lead-sheathed cables; COF by conduit type (steel/PVC/HDPE/FRP) and lubrication condition; jam ratio safe zones (danger: 2.7–3.1); NEC 300.34 bend radius multipliers.

Electrical Engineeringparameter type: MAX PULLING TENSION10 rowsPage 2 of 3
parameter typerecord idcmil area (cmil)conductor materialconductor sizestandardunitvalue max
MAX PULLING TENSIONPULL TENSION CU 10AWG10,380copper10 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf83
MAX PULLING TENSIONPULL TENSION CU 12AWG6,530copper12 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf52.2
MAX PULLING TENSIONPULL TENSION CU 14AWG4,110copper14 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf32.9
MAX PULLING TENSIONPULL TENSION CU 1AWG83,690copper1 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf670
MAX PULLING TENSIONPULL TENSION CU 1 0AWG105,600copper1/0 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf845
MAX PULLING TENSIONPULL TENSION CU 250KCMIL250,000copper250 KCMILIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf2,000
MAX PULLING TENSIONPULL TENSION CU 2AWG66,360copper2 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf531
MAX PULLING TENSIONPULL TENSION CU 2 0AWG133,100copper2/0 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf1,065
MAX PULLING TENSIONPULL TENSION CU 350KCMIL350,000copper350 KCMILIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf2,800
MAX PULLING TENSIONPULL TENSION CU 3 0AWG167,800copper3/0 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf1,342