Home/Reference Data/Pf Correction/PF_0.82_TO_1.00 to PF_0.90_TO_1.00

Pf Correction: PF_0.82_TO_1.00 to PF_0.90_TO_1.00

Power factor correction � kVAR per kW multipliers for correcting power factor from original to target values per IEEE 141 (Red Book)

Electrical Engineeringcorrection_id: PF_0.82_TO_1.00 to PF_0.90_TO_1.005 rows
correction idkvar per kw (kVAR/kW)original pf (dimensionless)original pf angle deg (deg)target pf (dimensionless)target pf angle deg (deg)
PF_0.82_TO_1.000.6980.8234.9210
PF_0.84_TO_0.950.31730.8432.860.9518.19
PF_0.86_TO_0.950.26470.8630.680.9518.19
PF_0.88_TO_0.950.21110.8828.360.9518.19
PF_0.90_TO_1.000.48430.925.8410