Home/Reference Data/Pf Correction/PF_0.50_TO_0.85 to PF_0.60_TO_1.00

Pf Correction: PF_0.50_TO_0.85 to PF_0.60_TO_1.00

Power factor correction � kVAR per kW multipliers for correcting power factor from original to target values per IEEE 141 (Red Book)

Electrical Engineeringcorrection_id: PF_0.50_TO_0.85 to PF_0.60_TO_1.005 rows
correction idkvar per kw (kVAR/kW)original pf (dimensionless)original pf angle deg (deg)target pf (dimensionless)target pf angle deg (deg)
PF_0.50_TO_0.851.11230.5600.8531.79
PF_0.50_TO_0.951.40340.5600.9518.19
PF_0.55_TO_0.901.03420.5556.630.925.84
PF_0.60_TO_0.850.71360.653.130.8531.79
PF_0.60_TO_1.001.33330.653.1310