Home/Reference Data/Pf Correction/PF_0.76_TO_0.90 to PF_0.82_TO_0.85

Pf Correction: PF_0.76_TO_0.90 to PF_0.82_TO_0.85

Power factor correction � kVAR per kW multipliers for correcting power factor from original to target values per IEEE 141 (Red Book)

Electrical Engineeringcorrection_id: PF_0.76_TO_0.90 to PF_0.82_TO_0.855 rows
correction idkvar per kw (kVAR/kW)original pf (dimensionless)original pf angle deg (deg)target pf (dimensionless)target pf angle deg (deg)
PF_0.76_TO_0.900.37080.7640.540.925.84
PF_0.76_TO_1.000.85520.7640.5410
PF_0.78_TO_0.950.47360.7838.740.9518.19
PF_0.80_TO_0.900.26570.836.870.925.84
PF_0.82_TO_0.850.07830.8234.920.8531.79