Nec Ocpd Ratings: 430.52(C)(1)

instantaneous trip breaker ac squirrel cage design b 1100A to inverse time breaker 2017 single phase 250pct

NEC overcurrent protective device (OCPD) ratings — standard ampere ratings for fuses and circuit breakers per Section 240.6(A), motor branch circuit protection per 430.52(C)(1), overload relay sizing per 430.32, and transformer OCPD sizing per 450.3

Electrical Engineeringnec section: 430.52(C)(1)10 rowsPage 3 of 6
nec sectionrecord iddescriptiondevice typemax percent of flcmotor typenec tablerating amp (A)standard
430.52(C)(1)instantaneous trip breaker ac squirrel cage design b 1100AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakerac squirrel cage design b1,100NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker ac squirrel cage other 800AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakerac squirrel cage other800NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker dc constant voltage 250AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakerdc constant voltage250NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker single phase 800AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakersingle phase800NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker synchronous 800AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakersynchronous800NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker wound rotor 800AMaximum OCPD for motor branch circuit — % of motor FLCinstantaneous trip breakerwound rotor800NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)inverse time breaker 2017 ac polyphase other than wound rotor 250pctMotor branch-circuit protection: inverse time breaker for AC polyphase motors other than wound-rotor — max 250% of full-load currentinverse time breaker250AC polyphase motors other than wound-rotor430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)inverse time breaker 2017 dc constant voltage 150pctMotor branch-circuit protection: inverse time breaker for DC (constant voltage) — max 150% of full-load currentinverse time breaker150DC (constant voltage)430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)inverse time breaker 2017 design b energy efficient 250pctMotor branch-circuit protection: inverse time breaker for Design B energy-efficient — max 250% of full-load currentinverse time breaker250Design B energy-efficient430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)inverse time breaker 2017 single phase 250pctMotor branch-circuit protection: inverse time breaker for Single-phase motors — max 250% of full-load currentinverse time breaker250Single-phase motors430.52NEC (NFPA 70) 2017 Edition Table 430.52