Nec Ocpd Ratings: 430.52(C)(1)

dual element time delay fuse single phase 175A to instantaneous trip breaker 2017 wound rotor 800pct

NEC overcurrent protective device (OCPD) ratings — standard ampere ratings for fuses and circuit breakers per Section 240.6(A), motor branch circuit protection per 430.52(C)(1), overload relay sizing per 430.32, and transformer OCPD sizing per 450.3

Electrical Engineeringnec section: 430.52(C)(1)10 rowsPage 2 of 6
nec sectionrecord iddescriptiondevice typemax percent of flcmotor typenec tablerating amp (A)standard
430.52(C)(1)dual element time delay fuse single phase 175AMaximum OCPD for motor branch circuit — % of motor FLCdual element time delay fusesingle phase175NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)dual element time delay fuse synchronous 175AMaximum OCPD for motor branch circuit — % of motor FLCdual element time delay fusesynchronous175NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)dual element time delay fuse wound rotor 150AMaximum OCPD for motor branch circuit — % of motor FLCdual element time delay fusewound rotor150NEC (NFPA 70) Table 430.52(C)(1)
430.52(C)(1)instantaneous trip breaker 2017 ac polyphase other than wound rotor 800pctMotor branch-circuit protection: instantaneous trip breaker for AC polyphase motors other than wound-rotor — max 800% of full-load currentinstantaneous trip breaker800AC polyphase motors other than wound-rotor430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 dc constant voltage 250pctMotor branch-circuit protection: instantaneous trip breaker for DC (constant voltage) — max 250% of full-load currentinstantaneous trip breaker250DC (constant voltage)430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 design b energy efficient 1100pctMotor branch-circuit protection: instantaneous trip breaker for Design B energy-efficient — max 1100% of full-load currentinstantaneous trip breaker1,100Design B energy-efficient430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 single phase 800pctMotor branch-circuit protection: instantaneous trip breaker for Single-phase motors — max 800% of full-load currentinstantaneous trip breaker800Single-phase motors430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 squirrel cage other than design b 800pctMotor branch-circuit protection: instantaneous trip breaker for Squirrel cage - other than Design B energy-efficient — max 800% of full-load currentinstantaneous trip breaker800Squirrel cage - other than Design B energy-efficient430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 synchronous 800pctMotor branch-circuit protection: instantaneous trip breaker for Synchronous (see NEC 430.52 Note 3) — max 800% of full-load currentinstantaneous trip breaker800Synchronous (see NEC 430.52 Note 3)430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)instantaneous trip breaker 2017 wound rotor 800pctMotor branch-circuit protection: instantaneous trip breaker for Wound-rotor — max 800% of full-load currentinstantaneous trip breaker800Wound-rotor430.52NEC (NFPA 70) 2017 Edition Table 430.52