Nec Ocpd Ratings: 430.52(C)(1)

NEC overcurrent protective device (OCPD) ratings — standard ampere ratings for fuses and circuit breakers per Section 240.6(A), motor branch circuit protection per 430.52(C)(1), overload relay sizing per 430.32, and transformer OCPD sizing per 450.3

Electrical Engineeringnec_section: 430.52(C)(1)3 rows
nec sectionrecord iddescriptiondevice typemax percent of flcmotor typenec tablestandard
430.52(C)(1)dual_element_time_delay_fuse_2017_ac_polyphase_other_than_wound_rotor_175pctMotor branch-circuit protection: dual-element time-delay fuse for AC polyphase motors other than wound-rotor — max 175% of full-load currentdual_element_time_delay_fuse175AC polyphase motors other than wound-rotor430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)dual_element_time_delay_fuse_2017_dc_constant_voltage_150pctMotor branch-circuit protection: dual-element time-delay fuse for DC (constant voltage) — max 150% of full-load currentdual_element_time_delay_fuse150DC (constant voltage)430.52NEC (NFPA 70) 2017 Edition Table 430.52
430.52(C)(1)dual_element_time_delay_fuse_2017_design_b_energy_efficient_175pctMotor branch-circuit protection: dual-element time-delay fuse for Design B energy-efficient — max 175% of full-load currentdual_element_time_delay_fuse175Design B energy-efficient430.52NEC (NFPA 70) 2017 Edition Table 430.52