Nec Ocpd Ratings: 450.3(A)

NEC overcurrent protective device (OCPD) ratings — standard ampere ratings for fuses and circuit breakers per Section 240.6(A), motor branch circuit protection per 430.52(C)(1), overload relay sizing per 430.32, and transformer OCPD sizing per 450.3

Electrical Engineeringnec_section: 450.3(A)3 rows
nec sectionrecord idlocation typeprimary circuit breaker pctprimary fuse pctsecondary hv circuit breaker pctsecondary hv fuse pctsecondary lv protection pctstandardtransformer rated impedance
450.3(A)450.3A-any-z_6to10_primary_onlyAny location400%300%250%225%125%NEC (NFPA 70) 2017 Table 450.3(A)More than 6% and not more than 10%
450.3(A)450.3A-any-z_le6_primary_onlyAny location600%300%300%250%125%NEC (NFPA 70) 2017 Table 450.3(A)Not more than 6%
450.3(A)450.3A-supervised-any-no_secondarySupervised locations only300%250%Not requiredNot requiredNot requiredNEC (NFPA 70) 2017 Table 450.3(A)Any