Home/Reference Data/Hx Fouling Factors/sea_water to tubular__fuel_oil__water

Hx Fouling Factors: sea_water to tubular__fuel_oil__water

Heat exchanger fouling factors (fouling resistance) for various fluid services — single-fluid TEMA values plus combined (total dirt) fouling resistance for common shell-and-tube service pairs from Perry's CEH Table 11-3

Mechanical Engineeringservice_id: sea_water to tubular__fuel_oil__water4 rows
service idfluid servicefouling factor combined hhf (h·ft2·°F/Btu)fouling factor max m2k w (m2K/W)fouling factor min m2k w (m2K/W)hx typeshell sidestandardtube side
tubular__air_n2_compressed__water_brineAir/N2 compressed / Water or brine (gas-liquid)0.0050.0008810.000881shell-and-tubeAir or N2 (compressed)Perry's Chemical Engineers' Handbook, 8th Ed., Table 11-3Water or brine
tubular__chlorine__light_ht_oil_vapChlorine / Light heat-transfer oil (vaporizer)0.00150.0002640.000264shell-and-tubeChlorinePerry's Chemical Engineers' Handbook, 8th Ed., Table 11-3Light heat-transfer oil
tubular__dowtherm_vapor__dowtherm_liquidDowtherm vapor / Dowtherm liquid0.00150.0002640.000264shell-and-tubeDowtherm vaporPerry's Chemical Engineers' Handbook, 8th Ed., Table 11-3Dowtherm liquid
tubular__fuel_oil__waterFuel oil / Water0.0070.0012330.001233shell-and-tubeFuel oilPerry's Chemical Engineers' Handbook, 8th Ed., Table 11-3Water