Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Fuse Characteristics: CLASS T

t300 lt 0045A to t300 lt 0150A

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse class: CLASS T8 rowsPage 2 of 7
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 100kA A2s (A2s)peak lt 100kA A (A)standardvoltage rating V (V)
CLASS Tt300 lt 0045A45A45459,0007,600IEEE Std 3004.3-2020300
CLASS Tt300 lt 0050A50A505011,0008,000IEEE Std 3004.3-2020300
CLASS Tt300 lt 0070A70A707025,00010,000IEEE Std 3004.3-2020300
CLASS Tt300 lt 0080A80A808030,00010,700IEEE Std 3004.3-2020300
CLASS Tt300 lt 0090A90A909038,00011,600IEEE Std 3004.3-2020300
CLASS Tt300 lt 0110A110A11011050,00012,000IEEE Std 3004.3-2020300
CLASS Tt300 lt 0125A125A12512575,00013,000IEEE Std 3004.3-2020300
CLASS Tt300 lt 0150A150A15015088,00014,000IEEE Std 3004.3-2020300