Fuse Characteristics: CLASS J

j lt 0500A to j lt 0600A

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse class: CLASS J2 rowsPage 4 of 4
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 100kA A2s (A2s)i2t 200kA A2s (A2s)i2t 300kA A2s (A2s)i2t 50kA A2s (A2s)peak lt 100kA A (A)peak lt 200kA A (A)peak lt 300kA A (A)peak lt 50kA A (A)peak lt functionstandardvoltage rating V (V)
CLASS Jj lt 0500A500A5005002,000,00042,000IEEE Std 3004.3-2020600
CLASS Jj lt 0600A600A6006002,500,0002,500,0003,000,0002,500,00045,00070,000101,36735,000Y = 3E-07x2 + 0.15x + 26667IEEE Std 3004.3-2020600