Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Fuse Characteristics: CLASS G

g lt 0040A to g lt 0060A

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse class: CLASS G4 rowsPage 2 of 2
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 50kA A2s (A2s)peak lt 50kA A (A)standardvoltage rating V (V)
CLASS Gg lt 0040A40A404017,0008,500IEEE Std 3004.3-2020480
CLASS Gg lt 0045A45A454518,5009,000IEEE Std 3004.3-2020480
CLASS Gg lt 0050A50A505021,0009,500IEEE Std 3004.3-2020480
CLASS Gg lt 0060A60A606025,00010,500IEEE Std 3004.3-2020480

What else is in Engineering Database