Home/Reference Data/Equipment Sound Power/chiller_screw to compressor_screw

Equipment Sound Power: chiller_screw to compressor_screw

Equipment sound power levels (Lw) by octave band for HVAC and mechanical equipment, used in acoustic analysis per ASHRAE Applications Handbook

Mechanical Engineeringequipment_type: chiller_screw to compressor_screw5 rows
equipment typeLw 125Hz (dB)Lw 1kHz (dB)Lw 250Hz (dB)Lw 2kHz (dB)Lw 4kHz (dB)Lw 500Hz (dB)Lw 63Hz (dB)Lw 8kHz (dB)Lw dBA (dBA)capacity rangeequipment descriptionlocation
chiller_screw84808378748282698550-400 tonScrew chiller (50-400 ton)mechanical_room
chiller_scroll79757873697777648020-150 tonScroll chiller (20-150 ton)mechanical_room
compressor_centrifugal87838681778585728850-1000 HPCentrifugal compressor (50-1000 HP)mechanical_room
compressor_reciprocating8887898480888675905-100 HPReciprocating compressor (5-100 HP)mechanical_room
compressor_screw84808378748282698510-500 HPScrew compressor (10-500 HP)mechanical_room

This is a sample. Search the full equipment sound power dataset and 300+ more by creating a free account and accessing the database.