Home/Reference Data/Equipment Sound Power/air_terminal_fan_powered to boiler_medium

Equipment Sound Power: air_terminal_fan_powered to boiler_medium

Equipment sound power levels (Lw) by octave band for HVAC and mechanical equipment, used in acoustic analysis per ASHRAE Applications Handbook

Mechanical Engineeringequipment_type: air_terminal_fan_powered to boiler_medium5 rows
equipment typeLw 125Hz (dB)Lw 1kHz (dB)Lw 250Hz (dB)Lw 2kHz (dB)Lw 4kHz (dB)Lw 500Hz (dB)Lw 63Hz (dB)Lw 8kHz (dB)Lw dBA (dBA)capacity rangeequipment descriptionlocation
air_terminal_fan_powered444043383442422945200-3000 CFMFan-powered VAV boxabove_ceiling
air_terminal_grille322530221828331330100-1000 CFMReturn air grillewall
air_terminal_vav373035272333381835100-2000 CFMVariable air volume boxabove_ceiling
boiler_large86808477728284668510-50 MMBTU/hrLarge boiler (10-50 MMBTU/hr)mechanical_room
boiler_medium8175797267777961803-10 MMBTU/hrMedium boiler (3-10 MMBTU/hr)mechanical_room