Mechanical Engineeringequipment_type: air_handling_unit_large to air_terminal_diffuser5 rows
equipment typeLw 125Hz (dB)Lw 1kHz (dB)Lw 250Hz (dB)Lw 2kHz (dB)Lw 4kHz (dB)Lw 500Hz (dB)Lw 63Hz (dB)Lw 8kHz (dB)Lw dBA (dBA)capacity rangeequipment descriptionlocation
air_handling_unit_large94909387839292789520000-60000 CFMLarge air handling unit (20000-60000 CFM)mechanical_room
air_handling_unit_medium8480837773828268855000-20000 CFMMedium air handling unit (5000-20000 CFM)mechanical_room
air_handling_unit_rooftop8177807470797965825-25 tonRooftop packaged AHU (5-25 ton)rooftop
air_handling_unit_small7470736763727258751000-5000 CFMSmall air handling unit (1000-5000 CFM)mechanical_room
air_terminal_diffuser2720251713232882550-500 CFMSupply air diffuserceiling