Mechanical Engineeringequipment_type: boiler_small to chiller_centrifugal_small5 rows
equipment typeLw 125Hz (dB)Lw 1kHz (dB)Lw 250Hz (dB)Lw 2kHz (dB)Lw 4kHz (dB)Lw 500Hz (dB)Lw 63Hz (dB)Lw 8kHz (dB)Lw dBA (dBA)capacity rangeequipment descriptionlocation
boiler_small7670746762727456750.5-3 MMBTU/hrSmall boiler (0.5-3 MMBTU/hr)mechanical_room
chiller_absorption787377716775766278100-1500 tonAbsorption chiller (100-1500 ton)mechanical_room
chiller_air_cooled89858883798787749020-500 tonAir-cooled chiller (20-500 ton)outdoor
chiller_centrifugal_large969094878292947695300-2000 tonLarge centrifugal chiller (300-2000 ton)mechanical_room
chiller_centrifugal_small868084777282846685100-300 tonSmall centrifugal chiller (100-300 ton)mechanical_room