Explore the Engineering Database more efficiently by signing up for free. Sign up free
E36-220 — Switchgear
- Equipment Type
- Switchgear
- Class Code
- E36-220
- Description
- Switchgear, Insulated bus, >
- Failure Rate per Year (failures/year)
- 0.004929
- Failures (count)
- 2
- Mdt Hours (h)
- 0.78
- Mtbf Hours (h)
- 1,777,272
- Mttm Hours (h)
- 0.77
- Mttr Hours (h)
- 5
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 405.8
Source: IEEE Std 3006.8-2018 Table 2