E36-220 — Switchgear

Equipment Type
Switchgear
Class Code
E36-220
Description
Switchgear, Insulated bus, >
Failure Rate per Year (failures/year)
0.004929
Failures (count)
2
Mdt Hours (h)
0.78
Mtbf Hours (h)
1,777,272
Mttm Hours (h)
0.77
Mttr Hours (h)
5
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
405.8

Source: IEEE Std 3006.8-2018 Table 2