Explore the Engineering Database more efficiently by signing up for free. Sign up free

E36-130 — Switchgear

Equipment Type
Switchgear
Class Code
E36-130
Description
Switchgear, Bare bus, > 5 kV
Failure Rate per Year (failures/year)
0.016746
Failures (count)
15
Mdt Hours (h)
1.3
Mtbf Hours (h)
523,105
Mttm Hours (h)
1.28
Mttr Hours (h)
2.27
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
895.7

Source: IEEE Std 3006.8-2018 Table 2

Switchgear — class code E36-130 · description Switchgear, bare bus, > 5 kV · failure rate per year 0.0167462 failures/year · mtbf hours 523105 h · unit years 895.7 unit-years | Equipment Failure Rates | Engineering Database