Explore the Engineering Database more efficiently by signing up for free. Sign up free

E36-120 — Switchgear

Equipment Type
Switchgear
Class Code
E36-120
Description
Switchgear, Bare bus, > 600 V
Failure Rate per Year (failures/year)
0.00476
Failures (count)
4
Mdt Hours (h)
9.67
Mtbf Hours (h)
1,840,518
Mttm Hours (h)
6.59
Mttr Hours (h)
195.75
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
840.4

Source: IEEE Std 3006.8-2018 Table 2

Switchgear — class code E36-120 · description Switchgear, bare bus, > 600 V · failure rate per year 0.00475953 failures/year · mtbf hours 1840518 h · unit years 840.4 unit-years | Equipment Failure Rates | Engineering Database