Explore the Engineering Database more efficiently by signing up for free. Sign up free

H14-400 — Cooling Tower

Equipment Type
Cooling Tower
Class Code
H14-400
Description
Cooling tower, Evaporative Type (with fans, motors, and Internal Lift pump)
Failure Rate per Year (failures/year)
0.144195
Failures (count)
27
Mdt Hours (h)
4.78
Mtbf Hours (h)
60,751
Mttm Hours (h)
3.83
Mttr Hours (h)
6.25
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
187.2

Source: IEEE Std 3006.8-2018 Table 2

Cooling_Tower — class code H14-400 · description Cooling tower, evaporative type (with fans, motors, and internal lift pump) · failure rate per year 0.144195 failures/year · mtbf hours 60751 h · unit years 187.2 unit-years | Equipment Failure Rates | Engineering Database