Explore the Engineering Database more efficiently by signing up for free. Sign up free

H14-300 — Cooling Tower

Equipment Type
Cooling Tower
Class Code
H14-300
Description
Cooling tower, Atmospheric Type (with fans, motors, and Internal Lift pump)
Failure Rate per Year (failures/year)
0.483906
Failures (count)
502
Mdt Hours (h)
8.28
Mtbf Hours (h)
18,103
Mttm Hours (h)
4.34
Mttr Hours (h)
8.77
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
1,037.4

Source: IEEE Std 3006.8-2018 Table 2

Cooling_Tower — class code H14-300 · description Cooling tower, atmospheric type (with fans, motors, and internal lift pump) · failure rate per year 0.483906 failures/year · mtbf hours 18103 h · unit years 1037.4 unit-years | Equipment Failure Rates | Engineering Database