Explore the Engineering Database more efficiently by signing up for free. Sign up free
H14-100 — Cooling Tower
- Equipment Type
- Cooling Tower
- Class Code
- H14-100
- Description
- Cooling tower, Atmospheric Type (w/o fans, motors, and Internal Lift pump)
- Failure Rate per Year (failures/year)
- 0.074138
- Failures (count)
- 24
- Mdt Hours (h)
- 1.14
- Mtbf Hours (h)
- 118,158
- Mttm Hours (h)
- 0.99
- Mttr Hours (h)
- 88.92
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 323.7
Source: IEEE Std 3006.8-2018 Table 2