Explore the Engineering Database more efficiently by signing up for free. Sign up free

H14-100 — Cooling Tower

Equipment Type
Cooling Tower
Class Code
H14-100
Description
Cooling tower, Atmospheric Type (w/o fans, motors, and Internal Lift pump)
Failure Rate per Year (failures/year)
0.074138
Failures (count)
24
Mdt Hours (h)
1.14
Mtbf Hours (h)
118,158
Mttm Hours (h)
0.99
Mttr Hours (h)
88.92
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
323.7

Source: IEEE Std 3006.8-2018 Table 2

Cooling_Tower — class code H14-100 · description Cooling tower, atmospheric type (w/o fans, motors, and internal lift pump) · failure rate per year 0.0741377 failures/year · mtbf hours 118158 h · unit years 323.7 unit-years | Equipment Failure Rates | Engineering Database