H05-310 — Air Handling Unit

Equipment Type
Air Handling Unit
Class Code
H05-310
Description
Air Handling unit, Multizone
Failure Rate per Year (failures/year)
0.405892
Failures (count)
448
Mdt Hours (h)
9.97
Mtbf Hours (h)
21,582
Mttm Hours (h)
4.34
Mttr Hours (h)
6.18
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
1,103.7

Source: IEEE Std 3006.8-2018 Table 2