H05-140 — Air Handling Unit

Equipment Type
Air Handling Unit
Class Code
H05-140
Description
Air Handling unit, humid, Spray
Failure Rate per Year (failures/year)
0.368256
Failures (count)
38
Mdt Hours (h)
4.31
Mtbf Hours (h)
23,788
Mttm Hours (h)
1.59
Mttr Hours (h)
2.27
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
103.2

Source: IEEE Std 3006.8-2018 Table 2