H05-210 — Air Handling Unit
- Equipment Type
- Air Handling Unit
- Class Code
- H05-210
- Description
- Air Handling unit, Non-humid,
- Failure Rate per Year (failures/year)
- 0.221709
- Failures (count)
- 1,734
- Mdt Hours (h)
- 2.4
- Mtbf Hours (h)
- 39,511
- Mttm Hours (h)
- 1.88
- Mttr Hours (h)
- 4.95
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 7,821.1