H05-210 — Air Handling Unit

Equipment Type
Air Handling Unit
Class Code
H05-210
Description
Air Handling unit, Non-humid,
Failure Rate per Year (failures/year)
0.221709
Failures (count)
1,734
Mdt Hours (h)
2.4
Mtbf Hours (h)
39,511
Mttm Hours (h)
1.88
Mttr Hours (h)
4.95
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
7,821.1

Source: IEEE Std 3006.8-2018 Table 2

Air_Handling_Unit — class code H05-210 · failure rate per year 0.221709 failures/year · mtbf hours 39511 h · unit years 7821.1 unit-years · mttm hours 1.88 h | Equipment Failure Rates | Engineering Database