Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr mccb le10k10 rowsPage 3 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr mccb le10k24MCCB le10kA1.2624IEEE Std 3004.5-20254.05
xr mccb le10k25MCCB le10kA1.2425IEEE Std 3004.5-20253.87
xr mccb le10k26MCCB le10kA1.2326IEEE Std 3004.5-20253.71
xr mccb le10k27MCCB le10kA1.2227IEEE Std 3004.5-20253.57
xr mccb le10k28MCCB le10kA1.228IEEE Std 3004.5-20253.43
xr mccb le10k29MCCB le10kA1.1929IEEE Std 3004.5-20253.3
xr mccb le10k30MCCB le10kA1.1830IEEE Std 3004.5-20253.18
xr mccb le10k35MCCB le10kA1.1335IEEE Std 3004.5-20252.68
xr mccb le10k40MCCB le10kA1.0840IEEE Std 3004.5-20252.29
xr mccb le10k45MCCB le10kA1.0445IEEE Std 3004.5-20251.98