Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Circuit Breaker Ratings: xr mccb le10k

14 to 23

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr mccb le10k10 rowsPage 2 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr mccb le10k14MCCB le10kA1.4114IEEE Std 3004.5-20257.07
xr mccb le10k15MCCB le10kA1.3915IEEE Std 3004.5-20256.59
xr mccb le10k16MCCB le10kA1.3816IEEE Std 3004.5-20256.17
xr mccb le10k17MCCB le10kA1.3617IEEE Std 3004.5-20255.8
xr mccb le10k18MCCB le10kA1.3518IEEE Std 3004.5-20255.49
xr mccb le10k19MCCB le10kA1.3319IEEE Std 3004.5-20255.17
xr mccb le10k20MCCB le10kA1.3120IEEE Std 3004.5-20254.9
xr mccb le10k21MCCB le10kA1.3121IEEE Std 3004.5-20254.86
xr mccb le10k22MCCB le10kA1.2822IEEE Std 3004.5-20254.43
xr mccb le10k23MCCB le10kA1.2723IEEE Std 3004.5-20254.23

What else is in Engineering Database

Related data