Circuit Breaker Ratings: LVPCB_no_inst_shortcircuit
Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.
| voltage class | interrupting kA | breaker type | frame size A (A) | sc max kA 1058V (kA) | sc max kA 730V (kA) | sc min kA 1058V (kA) | sc min kA 730V (kA) | standard | trip system |
|---|---|---|---|---|---|---|---|---|---|
| LVPCB_no_inst_shortcircuit | 600 | LVPCB | 600 | — | 22 | — | 22 | IEEE Std 3004.5-2025 | no_instantaneous |
| LVPCB_no_inst_shortcircuit | 800 | LVPCB | 800 | 85 | 85 | 10 | 22 | IEEE Std 3004.5-2025 | no_instantaneous |
| LVPCB_no_inst_shortcircuit | 1,600 | LVPCB | 1,600 | 85 | 85 | 10 | 42 | IEEE Std 3004.5-2025 | no_instantaneous |
This is a sample. Search the full circuit breaker ratings dataset and 350+ more by creating a free account and accessing the database.