Home/Reference Data/Circuit Breaker Ratings/LVPCB_no_inst_shortcircuit

Circuit Breaker Ratings: LVPCB_no_inst_shortcircuit

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage_class: LVPCB_no_inst_shortcircuit3 rows
voltage classinterrupting kAbreaker typeframe size A (A)sc max kA 1058V (kA)sc max kA 730V (kA)sc min kA 1058V (kA)sc min kA 730V (kA)standardtrip system
LVPCB_no_inst_shortcircuit600LVPCB6002222IEEE Std 3004.5-2025no_instantaneous
LVPCB_no_inst_shortcircuit800LVPCB80085851022IEEE Std 3004.5-2025no_instantaneous
LVPCB_no_inst_shortcircuit1,600LVPCB1,60085851042IEEE Std 3004.5-2025no_instantaneous