Circuit Breaker Ratings: 145KV

Power circuit breaker preferred ratings per IEEE C37.06. Covers 15.5kV through 800kV. PK = voltage class, SK = interrupting rating (kA, Number type). Fields include continuous current, close-and-latch, TRV, and interrupting time.

Electrical Engineeringvoltage_class: 145KV3 rows
voltage classinterrupting kAclose latch current kA crest (kA)continuous current A (A)interrupting time cycles (cycles)rated max voltage kV (kV)rated trv kV peak (kV)short circuit current kA (kA)standard
145KV12.532.51,200514529012.5IEEE C37.06-2009
145KV20522,000514529020IEEE C37.06-2009
145KV25652,000514529025IEEE C37.06-2009

This is a sample. Search the full circuit breaker ratings dataset and 300+ more by creating a free account and accessing the database.