Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Circuit Breaker Ratings: xr mccb 10k 20k

24 to 45

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr mccb 10k 20k10 rowsPage 3 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr mccb 10k 20k24MCCB 10k 20kA1.0624IEEE Std 3004.5-20254.05
xr mccb 10k 20k25MCCB 10k 20kA1.0525IEEE Std 3004.5-20253.87
xr mccb 10k 20k26MCCB 10k 20kA1.0426IEEE Std 3004.5-20253.71
xr mccb 10k 20k27MCCB 10k 20kA1.0327IEEE Std 3004.5-20253.57
xr mccb 10k 20k28MCCB 10k 20kA1.0228IEEE Std 3004.5-20253.43
xr mccb 10k 20k29MCCB 10k 20kA1.0129IEEE Std 3004.5-20253.3
xr mccb 10k 20k30MCCB 10k 20kA130IEEE Std 3004.5-20253.18
xr mccb 10k 20k35MCCB 10k 20kA135IEEE Std 3004.5-20252.68
xr mccb 10k 20k40MCCB 10k 20kA140IEEE Std 3004.5-20252.29
xr mccb 10k 20k45MCCB 10k 20kA145IEEE Std 3004.5-20251.98

What else is in Engineering Database

Related data