Circuit Breaker Ratings: xr_mccb_10k_20k
Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.
| voltage class | interrupting kA | breaker type | multiplying factor (dimensionless) | power factor pct (%) | standard | xr ratio (dimensionless) |
|---|---|---|---|---|---|---|
| xr_mccb_10k_20k | 4 | MCCB_10k_20kA | 1.37 | 4 | IEEE Std 3004.5-2025 | 24.98 |
| xr_mccb_10k_20k | 5 | MCCB_10k_20kA | 1.35 | 5 | IEEE Std 3004.5-2025 | 19.97 |
| xr_mccb_10k_20k | 6 | MCCB_10k_20kA | 1.33 | 6 | IEEE Std 3004.5-2025 | 16.64 |
This is a sample. Search the full circuit breaker ratings dataset and 350+ more by creating a free account and accessing the database.