24 to 45

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr lvpcb unfused10 rowsPage 3 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr lvpcb unfused24LVPCB unfused124IEEE Std 3004.5-20254.05
xr lvpcb unfused25LVPCB unfused125IEEE Std 3004.5-20253.87
xr lvpcb unfused26LVPCB unfused126IEEE Std 3004.5-20253.71
xr lvpcb unfused27LVPCB unfused127IEEE Std 3004.5-20253.57
xr lvpcb unfused28LVPCB unfused128IEEE Std 3004.5-20253.43
xr lvpcb unfused29LVPCB unfused129IEEE Std 3004.5-20253.3
xr lvpcb unfused30LVPCB unfused130IEEE Std 3004.5-20253.18
xr lvpcb unfused35LVPCB unfused135IEEE Std 3004.5-20252.68
xr lvpcb unfused40LVPCB unfused140IEEE Std 3004.5-20252.29
xr lvpcb unfused45LVPCB unfused145IEEE Std 3004.5-20251.98