14 to 23

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr lvpcb unfused10 rowsPage 2 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr lvpcb unfused14LVPCB unfused1.0114IEEE Std 3004.5-20257.07
xr lvpcb unfused15LVPCB unfused115IEEE Std 3004.5-20256.59
xr lvpcb unfused16LVPCB unfused116IEEE Std 3004.5-20256.17
xr lvpcb unfused17LVPCB unfused117IEEE Std 3004.5-20255.8
xr lvpcb unfused18LVPCB unfused118IEEE Std 3004.5-20255.49
xr lvpcb unfused19LVPCB unfused119IEEE Std 3004.5-20255.17
xr lvpcb unfused20LVPCB unfused120IEEE Std 3004.5-20254.9
xr lvpcb unfused21LVPCB unfused121IEEE Std 3004.5-20254.86
xr lvpcb unfused22LVPCB unfused122IEEE Std 3004.5-20254.43
xr lvpcb unfused23LVPCB unfused123IEEE Std 3004.5-20254.23