Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Circuit Breaker Ratings: xr lvpcb fused

24 to 45

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr lvpcb fused10 rowsPage 3 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr lvpcb fused24LVPCB fused124IEEE Std 3004.5-20254.05
xr lvpcb fused25LVPCB fused125IEEE Std 3004.5-20253.87
xr lvpcb fused26LVPCB fused126IEEE Std 3004.5-20253.71
xr lvpcb fused27LVPCB fused127IEEE Std 3004.5-20253.57
xr lvpcb fused28LVPCB fused128IEEE Std 3004.5-20253.43
xr lvpcb fused29LVPCB fused129IEEE Std 3004.5-20253.3
xr lvpcb fused30LVPCB fused130IEEE Std 3004.5-20253.18
xr lvpcb fused35LVPCB fused135IEEE Std 3004.5-20252.68
xr lvpcb fused40LVPCB fused140IEEE Std 3004.5-20252.29
xr lvpcb fused45LVPCB fused145IEEE Std 3004.5-20251.98