Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Circuit Breaker Ratings: xr lvpcb fused

14 to 23

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage class: xr lvpcb fused10 rowsPage 2 of 4
voltage classinterrupting kAbreaker typemultiplying factor (dimensionless)power factor pct (%)standardxr ratio (dimensionless)
xr lvpcb fused14LVPCB fused1.0814IEEE Std 3004.5-20257.07
xr lvpcb fused15LVPCB fused1.0615IEEE Std 3004.5-20256.59
xr lvpcb fused16LVPCB fused1.0516IEEE Std 3004.5-20256.17
xr lvpcb fused17LVPCB fused1.0417IEEE Std 3004.5-20255.8
xr lvpcb fused18LVPCB fused1.0318IEEE Std 3004.5-20255.49
xr lvpcb fused19LVPCB fused1.0219IEEE Std 3004.5-20255.17
xr lvpcb fused20LVPCB fused120IEEE Std 3004.5-20254.9
xr lvpcb fused21LVPCB fused121IEEE Std 3004.5-20254.86
xr lvpcb fused22LVPCB fused122IEEE Std 3004.5-20254.43
xr lvpcb fused23LVPCB fused123IEEE Std 3004.5-20254.23

What else is in Engineering Database

Related data