Home/Reference Data/Ashrae Design Conditions/US_AK_Juneau to US_IA_Des_Moines

Ashrae Design Conditions: US_AK_Juneau to US_IA_Des_Moines

ASHRAE outdoor design conditions — heating and cooling design temperatures, wet-bulb temperatures, and daily ranges for cities worldwide per ASHRAE Fundamentals

Mechanical Engineeringcity_id: US_AK_Juneau to US_IA_Des_Moines5 rows
city idcooling db 1pct C (C)cooling db 1pct F (F)cooling wb 1pct C (C)cooling wb 1pct F (F)countrydaily range C (C)daily range F (F)elevation m (m)heating db 99 6pct C (C)heating db 99 6pct F (F)heating db 99pct C (C)heating db 99pct F (F)latitude (deg)longitude (deg)state provincestation name
US_AK_Juneau21.1701559US8.3157-20-4-17.2158.36-134.58AlaskaJuneau Intl AP
US_AZ_Phoenix43.311023.975US15273370.6332.23633.43-112.02ArizonaPhoenix Sky Harbor AP
US_CA_San_Jose33.9932068US1527150321.13437.36-121.93CaliforniaSan Jose Intl AP
US_FL_Jacksonville35.69626.179US10189-3.925-1.72930.49-81.69FloridaJacksonville Intl AP
US_IA_Des_Moines34.49425.678US12.222294-23.3-10-20.6-541.53-93.65IowaDes Moines Intl AP