Substation Clearances: 15KV to 115KV

Minimum electrical clearances for outdoor air-insulated substations per NESC Rule 235 and IEEE Std 1427. Includes phase-to-ground, phase-to-phase, fence, roadway and walkway clearances by voltage class.

Electrical Engineeringvoltage_class: 15KV to 115KV4 rows
voltage classbil basis kV (kV)clearance over roadway ft (ft)clearance over walkway ft (ft)clearance to fence ft (ft)min phase ground clearance in (in)min phase phase clearance in (in)nesc rulestandard
25KV1501812.589.59.5NESC_235IEEE Std 1312 / NESC 2023
38KV2001812.581313NESC_235IEEE Std 1312 / NESC 2023
69KV3502014101821NESC_235IEEE Std 1312 / NESC 2023
115KV55021.515.5102529NESC_235IEEE Std 1312 / NESC 2023