Substation Clearances: 138KV to 500KV
Minimum electrical clearances for outdoor air-insulated substations per NESC Rule 235 and IEEE Std 1427. Includes phase-to-ground, phase-to-phase, fence, roadway and walkway clearances by voltage class.
| voltage class | bil basis kV (kV) | clearance over roadway ft (ft) | clearance over walkway ft (ft) | clearance to fence ft (ft) | min phase ground clearance in (in) | min phase phase clearance in (in) | nesc rule | standard |
|---|---|---|---|---|---|---|---|---|
| 138KV | 650 | 22.5 | 16.5 | 10 | 28 | 34 | NESC_235 | IEEE Std 1312 / NESC 2023 |
| 161KV | 750 | 23.5 | 17.5 | 10 | 32 | 38 | NESC_235 | IEEE Std 1312 / NESC 2023 |
| 230KV | 900 | 25 | 19 | 11 | 42 | 50 | NESC_235 | IEEE Std 1312 / NESC 2023 |
| 345KV | 1,300 | 27.5 | 21.5 | 12 | 62 | 74 | NESC_235 | IEEE Std 1312 / NESC 2023 |
| 500KV | 1,800 | 32 | 26 | 13 | 97 | 116 | NESC_235 | IEEE Std 1312 / NESC 2023 |
This is a sample. Search the full substation clearances dataset and 300+ more by creating a free account and accessing the database.