Substation Clearances: 138KV to 500KV

Minimum electrical clearances for outdoor air-insulated substations per NESC Rule 235 and IEEE Std 1427. Includes phase-to-ground, phase-to-phase, fence, roadway and walkway clearances by voltage class.

Electrical Engineeringvoltage_class: 138KV to 500KV5 rows
voltage classbil basis kV (kV)clearance over roadway ft (ft)clearance over walkway ft (ft)clearance to fence ft (ft)min phase ground clearance in (in)min phase phase clearance in (in)nesc rulestandard
138KV65022.516.5102834NESC_235IEEE Std 1312 / NESC 2023
161KV75023.517.5103238NESC_235IEEE Std 1312 / NESC 2023
230KV9002519114250NESC_235IEEE Std 1312 / NESC 2023
345KV1,30027.521.5126274NESC_235IEEE Std 1312 / NESC 2023
500KV1,80032261397116NESC_235IEEE Std 1312 / NESC 2023

This is a sample. Search the full substation clearances dataset and 300+ more by creating a free account and accessing the database.