Short Circuit Data: transformer

300KVA to 75KVA

Typical equipment impedances (%Z) and X/R ratios for short circuit calculations per IEEE 141 (Red Book) and IEEE 551 (Violet Book). Covers transformers by kVA, utility sources by voltage level, cables, motor contributions, generators, and reactors.

Electrical Engineeringequipment type: transformer7 rowsPage 2 of 2
equipment typerating labelasym multiplier typical (dimensionless)impedance pct max (%)impedance pct min (%)impedance pct typical (%)mva base (MVA)standardxr ratio max (dimensionless)xr ratio min (dimensionless)xr ratio typical (dimensionless)
transformer300KVA1.195.7524.50.3IEEE 551-2006 Table 9-1; ANSI C57.12.01635
transformer30KVA1.1251.52.50.03IEEE 551-2006 Table 9-1; ANSI C57.12.013.522.5
transformer45KVA1.1251.52.50.045IEEE 551-2006 Table 9-1; ANSI C57.12.013.522.5
transformer5000KVA1.37.55.565IEEE 551-2006 Table 9-1; ANSI C57.12.00201215
transformer500KVA1.215.753.55.750.5IEEE 551-2006 Table 9-1; ANSI C57.12.01846
transformer750KVA1.225.7545.750.75IEEE 551-2006 Table 9-1; ANSI C57.12.01956
transformer75KVA1.145.751.53.10.075IEEE 551-2006 Table 9-1; ANSI C57.12.0142.53