Short Circuit Data: transformer

Typical equipment impedances (%Z) and X/R ratios for short circuit calculations per IEEE 141 (Red Book) and IEEE 551 (Violet Book). Covers transformers by kVA, utility sources by voltage level, cables, motor contributions, generators, and reactors.

Electrical Engineeringequipment_type: transformer3 rows
equipment typerating labelasym multiplier typical (dimensionless)impedance pct max (%)impedance pct min (%)impedance pct typical (%)mva base (MVA)notesxr ratio max (dimensionless)xr ratio min (dimensionless)xr ratio typical (dimensionless)
transformer10000KVA1.3386710Liquid-filled substation transformer351825
transformer1000KVA1.2464.55.751Dry-type or liquid; dual-voltage primary1067
transformer112.5KVA1.155.751.53.10.1125Dry-type LV distribution; most common small commercial size4.52.53.5