Short Circuit Data: motor_contribution

Typical equipment impedances (%Z) and X/R ratios for short circuit calculations per IEEE 141 (Red Book) and IEEE 551 (Violet Book). Covers transformers by kVA, utility sources by voltage level, cables, motor contributions, generators, and reactors.

Electrical Engineeringequipment_type: motor_contribution3 rows
equipment typerating labelnotesxr ratio max (dimensionless)xr ratio typical (dimensionless)
motor_contributionAGGREGATE_LV_LOADAggregate LV motor load (mixed); use 0.25 pu subtransient X on motor kVA2.51
motor_contributionINDUCTION_LVMotor subtransient reactance Xd approx 16.7%; contributes 4-6x FLA for 1-4 cycles21.2
motor_contributionINDUCTION_MVMV induction motors >250HP; Xd 16.7-20%; higher X/R than LV3.51.5

This is a sample. Search the full short circuit data dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE