Rack Infrastructure Specs: OCP BBU Module

bbu discharger input voltage max to bbu discharger output voltage no load

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP BBU Module10 rowsPage 3 of 5
component typespec parametermax valuemin valueparameter nametest conditionunitvalue
OCP BBU Modulebbu discharger input voltage maxDischarger input voltage maximum4.0 V/cell; assuming 11S6P 18650 Li-ionV44.0
OCP BBU Modulebbu discharger input voltage minDischarger input voltage minimum2.6 V/cell; assuming 11S6P 18650 Li-ionV28.6
OCP BBU Modulebbu discharger output capacitance maxDischarger output capacitance maximum per shelfmF60
OCP BBU Modulebbu discharger output current maxDischarger output current maximumSee spec sec 4.3.1 for peak loadA63.2
OCP BBU Modulebbu discharger output power maxDischarger output power maximumSee spec sec 4.3.1 for peak loadW3000
OCP BBU Modulebbu discharger output ripple voltage maxDischarger output ripple voltage maximumPeak to peakmVpp300
OCP BBU Modulebbu discharger output voltage boost limit maxDischarger output voltage boost limit for SOHBBU boost voltage up to discharge energy at CP mode (e.g. 1.5 kW)V51.5
OCP BBU Modulebbu discharger output voltage droop0.550.45Discharger output voltage droop 0% to 100% loadV0.5
OCP BBU Modulebbu discharger output voltage full load47.647.4Discharger output voltage at 100% loadV47.5
OCP BBU Modulebbu discharger output voltage no load48.147.9Discharger output voltage at 0% loadV48.0