Rack Infrastructure Specs: OCP BBU Module

bbu charger input power max to bbu discharger input current max

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP BBU Module10 rowsPage 2 of 5
component typespec parametermax valuemin valueparameter nametest conditionunitvalue
OCP BBU Modulebbu charger input power maxCharger input power maximumW250
OCP BBU Modulebbu charger input voltage maxCharger input voltage maximumV53
OCP BBU Modulebbu charger input voltage minCharger input voltage minimumAccepts busbar transient below 49V above 46.5V for <2msV49
OCP BBU Modulebbu charger input voltage typ5150.5Charger input voltage typical rangeV50.5
OCP BBU Modulebbu charger power max265130Charger total BBU input power from busbarW265
OCP BBU Modulebbu design lifeBBU design lifeFull power discharge time >240s at PCM threshold ≥4 years @35°Cyears8
OCP BBU Modulebbu discharge trigger time2.11.9Discharge mode activation time thresholdms2
OCP BBU Modulebbu discharge trigger voltageDischarge mode activation busbar voltage thresholdActivates when busbar voltage drops below 48.5V for 2ms (±0.1ms)V48.5
OCP BBU Modulebbu discharger efficiency minDischarger minimum efficiencyMinimum across max load at full input voltage range; fuse/hot-swap/oring included%97
OCP BBU Modulebbu discharger input current maxDischarger input current maximumA110