Rack Infrastructure Specs: OCP BBU Module

bbu discharger output voltage setpoint max to bbu sleep wakeup busbar voltage

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP BBU Module8 rowsPage 4 of 5
component typespec parameterparameter nametest conditionunitvalue
OCP BBU Modulebbu discharger output voltage setpoint maxDischarger output voltage setpoint maximumAt 50% loadV47.80
OCP BBU Modulebbu discharger output voltage setpoint minDischarger output voltage setpoint minimumAt 50% loadV47.70
OCP BBU Modulebbu discharger output voltage setpoint typDischarger output voltage setpoint typicalAt 50% loadV47.75
OCP BBU Modulebbu discharger output voltage total regulation maxDischarger output voltage total regulation maximumIncluding load transientV49.5
OCP BBU Modulebbu discharger output voltage total regulation minDischarger output voltage total regulation minimumIncluding load transientV46.0
OCP BBU Modulebbu discharger startup time maxDischarger startup time maximumFrom discharger activation to output fully ramped up including peak load 150%ms2
OCP BBU Modulebbu operation mode standby power maxBBU standby mode total power consumption maxIncluding fan powerW15
OCP BBU Modulebbu sleep wakeup busbar voltageSleep mode wakeup busbar voltage thresholdBBU wakes when busbar >46V for 100-200ms with PSKILL lowV46