Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 10 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM10.0 10-20.281011.9610.000755100.8031ASHRAE Fundamentals 2017 Ch.11.18
STD ATM10.0 10010.021029.2850.007631000.812ASHRAE Fundamentals 2017 Ch.19.94
STD ATM10.0 20-11.951013.8680.001511200.8041ASHRAE Fundamentals 2017 Ch.12.29
STD ATM10.0 30-6.781015.7780.00227300.8051ASHRAE Fundamentals 2017 Ch.13.26
STD ATM10.0 40-2.971017.6940.00303400.806ASHRAE Fundamentals 2017 Ch.14.19
STD ATM10.0 500.071019.6140.003792500.807ASHRAE Fundamentals 2017 Ch.15.1
STD ATM10.0 602.611021.5380.004556600.808ASHRAE Fundamentals 2017 Ch.16.02
STD ATM10.0 704.81023.4680.005321700.809ASHRAE Fundamentals 2017 Ch.16.96
STD ATM10.0 806.731025.4020.006089800.81ASHRAE Fundamentals 2017 Ch.17.93
STD ATM10.0 908.461027.3410.006859900.811ASHRAE Fundamentals 2017 Ch.18.92