Psychrometric Properties: STD ATM

15.0 10 to 15.0 90

Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 11 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM15.0 10-16.411517.7420.001049100.8177ASHRAE Fundamentals 2017 Ch.14.07
STD ATM15.0 10015.031542.0160.0106471000.8303ASHRAE Fundamentals 2017 Ch.114.97
STD ATM15.0 20-7.781520.4030.002101200.8191ASHRAE Fundamentals 2017 Ch.15.69
STD ATM15.0 30-2.421523.0720.003156300.8204ASHRAE Fundamentals 2017 Ch.17.04
STD ATM15.0 401.531525.7510.004216400.8218ASHRAE Fundamentals 2017 Ch.18.25
STD ATM15.0 504.691528.4390.005279500.8232ASHRAE Fundamentals 2017 Ch.19.4
STD ATM15.0 607.331531.1360.006345600.8246ASHRAE Fundamentals 2017 Ch.110.52
STD ATM15.0 709.61533.8420.007415700.826ASHRAE Fundamentals 2017 Ch.111.62
STD ATM15.0 8011.611536.5580.008489800.8274ASHRAE Fundamentals 2017 Ch.112.73
STD ATM15.0 9013.41539.2820.009566900.8289ASHRAE Fundamentals 2017 Ch.113.84