Psychrometric Properties: STD ATM

0.0 10 to 0.0 90

Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 9 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM0.0 10-28.0800.9390.000375100.7743ASHRAE Fundamentals 2017 Ch.1-4.64
STD ATM0.0 1000.0109.440.0037741000.7785ASHRAE Fundamentals 2017 Ch.1-0.13
STD ATM0.0 20-20.3301.8790.000751200.7747ASHRAE Fundamentals 2017 Ch.1-4.53
STD ATM0.0 30-15.5402.820.001128300.7752ASHRAE Fundamentals 2017 Ch.1-4.29
STD ATM0.0 40-12.0103.7620.001504400.7757ASHRAE Fundamentals 2017 Ch.1-3.95
STD ATM0.0 50-9.1904.7060.001882500.7761ASHRAE Fundamentals 2017 Ch.1-3.5
STD ATM0.0 60-6.8405.650.002259600.7766ASHRAE Fundamentals 2017 Ch.1-2.96
STD ATM0.0 70-4.8106.5960.002637700.7771ASHRAE Fundamentals 2017 Ch.1-2.35
STD ATM0.0 80-3.0307.5430.003016800.7776ASHRAE Fundamentals 2017 Ch.1-1.67
STD ATM0.0 90-1.4408.4910.003395900.778ASHRAE Fundamentals 2017 Ch.1-0.93