Nuclear Seismic Qualification: tank_vertical
Seismic qualification requirements for nuclear power plant safety-related equipment per IEEE 344-2013, NRC Regulatory Guide 1.100 Rev.4, and NRC RG 1.60/1.61. Covers equipment seismic categories (Class 1E, Category I/II, non-seismic), test levels (OBE/SSE in g), Required Response Spectra (RRS) frequency ranges, damping ratios, fragility parameters (median capacity Am, randomness beta_R, uncertainty beta_U, HCLPF) by equipment class (switchgear, MCC, I&C panels, diesel generators, pumps, valves, piping, tanks), and anchorage design requirements.
| equipment category | qualification parameter | description | notes | parameter unit | parameter value max | parameter value min | parameter value typical | qualification method | seismic category |
|---|---|---|---|---|---|---|---|---|---|
| tank_vertical | fragility_median_capacity_Am_g | Median seismic capacity for vertical tanks (RWST, water storage) in Category I service. | Sloshing wave height and base shear govern; impulsive and convective modes both contribute per ACI 350.3. | g | 3 | 0.4 | 1 | fragility_analysis | Class_1E_Seismic_Category_I |
This is a sample. Search the full nuclear seismic qualification dataset and 300+ more by creating a free account and accessing the database.