Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: RC10 rowsPage 4 of 5
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
RCRC-40#63506763RC-40office open
RCRC-40#800050318,000RC-40office open
RCRC-45#100055451,000RC-45restaurant
RCRC-45#1255562125RC-45restaurant
RCRC-45#200055412,000RC-45restaurant
RCRC-45#2505555250RC-45restaurant
RCRC-45#400055384,000RC-45restaurant
RCRC-45#5005550500RC-45restaurant
RCRC-45#63557163RC-45restaurant
RCRC-45#800055368,000RC-45restaurant